Ground Water Replacement of Polymer Ultra Filtration System

ItN Nanovation started its ground water pre-filtration development in 2009 with a piloting plant for its first client in Buraydah, Qassim.

The existing plant using polymer ultra filtration system was operating under unstable conditions at high operational expenses. The client's focus was an improvement of the qualities by implementing a new ultra filtration system. After three months piloting ItN had reached complete satisfaction of the Client.
Only three months later the first CFM Systems® trains with a capacity of 600 m3/hr was set into operation. One year later, two additional trains were installed. All three trains have been running stably and reliably.

Client    

  • MOWE Ministry of Water & Electricity Directorate Qassim, Saudi Arabia
  • CWC Operation & Maintenance Company

Project Status    

  • July - August 2010 Installation & Commissioning of first filtration train 14,000 m³/d
  • March 2011 Installation & Commissioning of additional two filtration trains with 28,000 m³/d

Project Targets    

  • Removal of Iron, Manganese and Radium
  • Improvement of filtered water quality
  • Improvement of recovery rate

Capacity    

  • 42,000 m³/d

Parameter

Unit

Raw Water

Existing Polymer UF

CFM Systems

Iron

ppm

1.4–4.0

0.02–0.05

< 0.02

Manganese + HMO Manganese

ppm

0.3–2.9

0.03–0.05

< 0.02

Radium Total

pCi/L

70.0

49.0
(only 30% removal due to limitations for HMO dosage)

< 10.0
(up to 86% due to targeted HMO dosage)

Turbidity

NTU

2.15

0.2–0.3

0.15 (avg)

SDI

2–3

0.28 (avg)

Recovery Rate

%

85–88

99

Membrane Replacement

USD/m³

0.125
(after 6–9 months)

0.000
ZERO replacement since start of operation

Power Consumption

kWhr/m³

0.120

0.106

USD/m³

0.0083

0.0073

CIP Chemical Consumption

USD/m³

0.0030

0.0001

Total OPEX


USD/m³

0.1363

0.0074

USD/year

2.089 Mio

0.113 Mio

%

100.0

5.4

Thanks to the improved quality of water filtered by CFM Systems® all subsequent process steps, e.g. cartridge filters and reverse osmosis membranes are operating under very stable conditions. Replacement and chemical cleaning intervals have been extended, resulting in additional and significant OPEX savings.

The targeted implementation of a radium removal process by HMO adsorption led to an improved product water Quality, meeting all international standards for drinking water quality. After blending, the total radium concentration is now permanently less than 5.0 pCi/L.

In addition, annual water savings of about 800,000 m³ have been generated by the increased recovery rate of CFM Systems®. The existing backwash waste recovery systems have been put out of operation, simplyfying the plant's operation to a great extent.

Assembly of Filtration Racks

Assembled Filtration Racks

Installed Filtration Rack

Installed Filtration Racks

Water qualities (filtered water, raw water, backwash
waste water)